1
/
/
9
PayPal, credit cards. Download editable-PDF and invoice in 1 second!
GB 25204-2010 English PDF
GB 25204-2010 English PDF
Normaalihinta
$105.00 USD
Normaalihinta
Alennushinta
$105.00 USD
Yksikköhinta
/
kohti
Noudon saatavuutta ei voitu ladata
Delivery: 2 working-hours manually (Sales@ChineseStandard.net)
Need delivered in 3-second? USA-Site: GB 25204-2010
Get Quotation: Click GB 25204-2010 (Self-service in 1-minute)
Historical versions (Master-website): GB 25204-2010
Preview True-PDF (Reload/Scroll-down if blank)
GB 25204-2010: Auto tracking and targeting jet suppression system
GB 25204-2010
NATIONAL STANDARD OF THE
PEOPLE?€?S REPUBLIC OF CHINA
ICS 13.220.10
C 84
Auto Tracking and Targeting Jet Suppression System
ISSUED ON: SEPTEMBER 26, 2010
IMPLEMENTED ON: MARCH 1, 2011
Issued by: General Administration of Quality Supervision, Inspection and
Quarantine;
Standardization Administration of the People?€?s Republic of
China.
Table of Contents
Foreword ... 3??
1 Scope ... 4??
2 Normative References ... 4??
3 Terms and Definitions ... 4??
4 Classification and Model ... 5??
5 Performance Requirements ... 6??
6 Test Methods ... 9??
7 Inspection Rules ... 13??
8 Marking, Packaging, Storage, Transportation and Instruction Manual ... 14??
Appendix A (normative) Test Procedure of Automatic Tracking and Targeting Jet
Suppression System ... 16??
Auto Tracking and Targeting Jet Suppression System
1 Scope
This Standard stipulates the definition, classification, model, performance
requirements, test methods, inspection rules, marking, packaging, storage,
transportation and instruction manual of auto tracking and targeting jet suppression
system (hereinafter referred to as system).
This Standard is applicable to various auto tracking and targeting jet suppression
systems, which take water or foam mixture as the jet medium; utilize infrared rays,
digital images or other fire detection components for automatic targeting of early fires;
adopt automatic control technology to implement fire suppression.
2 Normative References
Through the reference in this Standard, clauses of the following documents become
clauses of this Standard. In terms of references with a specific date, all the subsequent
modification sheets (excluding the corrected content) or the revised editions are not
applicable to this Standard. However, all parties that reach an agreement in
accordance with this Standard are encouraged to explore the possibility of adopting
the latest version of these documents. In terms of references without a specific date,
the latest version is applicable to this Standard.
GB/T 2423.1-2008 Environmental Testing for Electric and Electronic Products - Part 2:
Test Methods - Tests A: Cold (IEC 60068-2-1:2007, IDT)
GB/T 2423.2-2008 Environmental Testing for Electric and Electronic Products - Part 2:
Test Methods - Tests B: Dry Heat (IEC 60068-2-2:2007, IDT)
GB/T 2423.3-2006 Environmental Testing for Electric and Electronic Products - Part 2:
Testing Method - Test Cab: Damp Heat, Steady State (IEC 60068-2-78:2001, IDT)
GB/T 2423.10-2008 Environmental Testing for Electric and Electronic Products - Part
2: Tests Methods - Test Fc: Vibration (IEC 60068-2-6:1995, IDT)
GB 4351.1-2005 Portable Fire Extinguishers - Part 1: Performance and Construction
(ISO 7165:1999, NEQ)
3 Terms and Definitions
The following terms and definitions are applicable to this Standard.
3.1 Auto Tracking and Targeting Jet Suppression System
Auto tracking and targeting jet suppression system refers to various indoor and outdoor
fixed jet suppression systems which utilize infrared rays, digital images or other fire
detection components to detect fire and temperature for automatic tracking and
targeting of early fires; adopt the mode of automatic control to implement fire
suppression. The system is constituted of fire suppression device, which is equipped
with detection component and automatic control part, as well as fire-fighting liquid
supply part. The fire suppression device is divided into automatic tracking and targeting
fire cannon suppression device (hereinafter referred to as automatic fire cannon
suppression device) and automatic tracking and targeting jet suppression device
(hereinafter referred to as automatic jet suppression device).
3.2 Targeting Time
Targeting time refers to the time from the start of test fire to the start of system jet.
3.3 Jet Radius
Jet radius refers to the length of the horizontal projection of the fire suppression device
to the farthest jet landing point, or, the radius of the circular projection of the ground
plane of the maximum jet protection range.
3.4 Maximum Protection Radius
Maximum protection radius refers to 90% of the length of the horizontal projection of
the fire suppression device to the farthest jet landing point, or, the radius of the circular
projection of the ground plane of effective spray projection range.
3.5 Monitory Radius
Monitory radius refers to the length of the horizontal projection of the detection
component of the fire suppression device to the center point of test fire that can be
effectively detected.
3.6 Working Pressure
Working pressure refers to fire suppression device?€?s rated outlet pressure.
4 Classification and Model
4.1 Classification
4.1.1 In accordance with flow, it may be classified into:
a) Rated flow is larger than 16 L/s: automatic fire cannon suppression device;
able to normally start and jet.
5.5 Insulation Resistance
In accordance with 6.6, fire suppression device shall receive insulation resistance test.
The insulation resistance between the external live terminals of the fire suppression
device and the casing shall be larger than 20 M???.
5.6 Dielectric Strength
In accordance with 6.7, fire suppression device shall receive dielectric strength test. It
shall be able to withstand voltage test for 1 min under the frequency of 50 Hz and the
voltage of 1,500 V. There shall be no phenomenon of breakdown or flashover.
5.7 Resistance to Ambient Light Interference
In accordance with 6.8, fire suppression device shall receive ambient light interference
test. During the test, the fire suppression device shall not trigger malfunctions, such as
starting and jetting.
5.8 Voltage Fluctuation Adaptability
In accordance with 6.9, fire suppression device shall receive voltage fluctuation
adaptability test. Within the rated voltage range of -10% ~ + 10%, it shall be able to
normally start and function.
5.9 Vibration Resistance
In accordance with 6.10, fire suppression device shall receive vibration resistance test.
After the test, the fire suppression device shall not manifest shedding, cracking or
obvious deformation; it shall be able to normally function.
5.10 Fire Suppression Performance
In accordance with 6.11, fire suppression device shall receive fire suppression
performance test. Starting from automatic jetting, within 3 min, the automatic fire
cannon suppression device and injection-type automatic jet suppression device shall
extinguish Level-1A fire suppression; within 6 min, spraying-type automatic jet
suppression device shall extinguish Level-1A fire suppression.
5.11 Requirements for Automatic Control
5.11.1 Requirements for intelligent detection and targeting and linkage decision
management
Fire suppression device shall be equipped with the function of intelligent detection and
targeting and linkage decision management, which shall be normally functioning.
angle and horizontal slewing angle of fire suppression device. The result shall comply
with the requirements in 5.1.
6.2 Performance Test
6.2.1 Measurement of rated pressure, flow, maximum protection radius, jet
radius and monitoring radius
Fix the fire suppression device at the minimum installation height. On the test pipeline,
install a flowmeter with an accuracy of not lower than ?? 1%; a pressure gauge with an
accuracy of not less than Level-1.6 and a measuring range of (0 ~ 2.5) MPa.
Manually control the nozzle to be in a horizontal state. Turn on the fire suppression
device to let it jet; maintain it at the rated working pressure; then, jet under the rated
pressure. After around 1 min, use a tape with an accuracy of ?? 1 cm to measure the
distance from the farthest trace to the projection directly underneath the nozzle, which
is the jet radius. 90% of the jet radius (rounded off) is the maximum protection radius.
Ignite the test fire; use a tape with an accuracy of ?? 1 cm to measure the length of the
horizontal projection of the center point of the test fire that can be effectively detected
by the detection component of the system, which is the monitoring radius.
The flow may be directly measured through a calibrated flowmeter. Or, in accordance
with the flow of fire suppression device, an appropriate volume of measuring tank may
be selected. Wait till it reaches the rated pressure and becomes stable, turn to the
measuring tank for jetting; the jetting time shall be not less than 30 s; immediately
remove it. Then, measure the volume or the mass of water in the measuring tank.
Through calculation, obtain the flow of the fire suppression device.
The test result shall all comply with the requirements in Table 1.
6.2.2 Measurement of targeting time
Respectively fix the fire suppression device at the minimum installation height and the
maximum installation height. At the measured maximum protection radius, use test fire
to induce the system to initiate the action of targeting, aim at the target and jet. Use an
electronic stopwatch with an accuracy of not lower than ?? 0.1 s to measure the time
from the start of the test fire to the start of the jet of the fire suppression device, which
is the targeting time. The measurement result shall comply with the stipulations in Table
1. The test fire is: add 30 mm height of clean water to a 570 mm diameter oil pan
(height: 70 mm), then, add 500 mL of automotive gasoline; ignite the gasoline on the
oil pan.
6.3 High Temperature Test
In accordance with GB/T 2423.2-2008, conduct the test. Connect the system to the
power supply, so that it could enter the normal monitoring state. Put the fire
6.9 Voltage Fluctuation Adaptability Test
Use a voltage regulator and electrotechnical instrument to respectively adjust the
power supply voltage to ?? 10% of the rated voltage. The test result shall comply with
the requirements in 5.8.
6.10 Vibration Resistance Test
6.10.1 The test method shall comply with the requirements in GB/T 2423.10-2008.
During the test, the fire suppression test shall be in non-working state. The test
conditions shall comply with the following stipulations:
a) Range of frequency cycle: 10 Hz ~ 150 Hz ~ 10 Hz;
b) Amplitude (single amplitude): 0.19 mm;
c) Scanning rate: one octave / min;
d) Vibration direction: three directions: XYZ;
e) Frequency-sweeping number: 2 frequency-sweeping cycles.
6.10.2 In accordance with the result of vibration response, respectively conduct the
test in accordance with the following three circumstances. Each test shall be
successively conducted in the three directions XYZ of the sample:
a) When resonance frequency is not found, at the frequency of 150 Hz, conduct
fixed frequency vibration test with the amplitude of 0.19 mm and the duration
of 10 min;
b) When there are not more than 4 resonance frequencies being found, on each
resonance point, conduct resonance test with the set amplitude of 0.19 mm
and the duration of 10 min;
c) When there are more than 4 resonance frequencies being found, within the
frequency cycle range of 10 Hz ~ 150 Hz ~ 10 Hz, conduct resonance test
with the amplitude of 0.19 mm and the frequency-sweeping rate of double
frequency / min. The duration of resonance is 1 h in each direction.
The test result shall comply with the requirements in 5.9.
6.11 Fire Suppression Test
6.11.1 Automatic fire cannon suppression device and injection-type automatic
jet suppression device
At the minimum installation height and the maximum installation height, respectively
place Level-1A fire test model inside the maximum protection radius of the fire
c) When production is resumed after one year of suspension, or, normal
production exceeds two years;
d) When a national quality supervision institution proposes a request for type
inspection.
7.1.2 The content of type inspection is all the items stipulated in this Standard. The
inspection result shall all satisfy the stipulations of this Standard.
7.1.3 The quantity of test samples for type inspection is 3 sets. The test procedure
shall comply with the stipulations of Appendix A.
7.2 Exit-factory Inspection
7.2.1 Before exiting factory, exit-factory inspection shall be conducted.
7.2.2 Exit-factory inspection shall be conducted in accordance with the stipulations in
5.1, 5.2, 5.3, 5.4, 5.5, 5.6, 5.7, 5.8, 5.9, 5.13 and 5.15. The result shall all comply with
the stipulations of this Standard.
8 Marking, Packaging, Storage, Transportation and
Instruction Manual
8.1 Marking
8.1.1 The nameplate of product shall include the following content: manufacturer name
and trademark, product name, model and specification, serial No. of implemented
standard, product No., working pressure, flow, jet flow radius, maximum protection
radius, monitoring radius, minimum and maximum installation height, etc.
8.1.2 The surface of packaging box shall be printed with product name, specification,
quantity, external dimensions of packaging box, gross weight, manufacturer name,
address and contact information.
8.2 Packaging
The packaging of product shall ensure that product is not damaged or loosened in
normal transportation, and that product complies with user?€?s demands and the
regulations of the transportation department.
8.3 Storage
The storage warehouse shall be well-ventilated, dry and clean. Products shall not be
heavily pressed.
8.4 Transportation
Need delivered in 3-second? USA-Site: GB 25204-2010
Get Quotation: Click GB 25204-2010 (Self-service in 1-minute)
Historical versions (Master-website): GB 25204-2010
Preview True-PDF (Reload/Scroll-down if blank)
GB 25204-2010: Auto tracking and targeting jet suppression system
GB 25204-2010
NATIONAL STANDARD OF THE
PEOPLE?€?S REPUBLIC OF CHINA
ICS 13.220.10
C 84
Auto Tracking and Targeting Jet Suppression System
ISSUED ON: SEPTEMBER 26, 2010
IMPLEMENTED ON: MARCH 1, 2011
Issued by: General Administration of Quality Supervision, Inspection and
Quarantine;
Standardization Administration of the People?€?s Republic of
China.
Table of Contents
Foreword ... 3??
1 Scope ... 4??
2 Normative References ... 4??
3 Terms and Definitions ... 4??
4 Classification and Model ... 5??
5 Performance Requirements ... 6??
6 Test Methods ... 9??
7 Inspection Rules ... 13??
8 Marking, Packaging, Storage, Transportation and Instruction Manual ... 14??
Appendix A (normative) Test Procedure of Automatic Tracking and Targeting Jet
Suppression System ... 16??
Auto Tracking and Targeting Jet Suppression System
1 Scope
This Standard stipulates the definition, classification, model, performance
requirements, test methods, inspection rules, marking, packaging, storage,
transportation and instruction manual of auto tracking and targeting jet suppression
system (hereinafter referred to as system).
This Standard is applicable to various auto tracking and targeting jet suppression
systems, which take water or foam mixture as the jet medium; utilize infrared rays,
digital images or other fire detection components for automatic targeting of early fires;
adopt automatic control technology to implement fire suppression.
2 Normative References
Through the reference in this Standard, clauses of the following documents become
clauses of this Standard. In terms of references with a specific date, all the subsequent
modification sheets (excluding the corrected content) or the revised editions are not
applicable to this Standard. However, all parties that reach an agreement in
accordance with this Standard are encouraged to explore the possibility of adopting
the latest version of these documents. In terms of references without a specific date,
the latest version is applicable to this Standard.
GB/T 2423.1-2008 Environmental Testing for Electric and Electronic Products - Part 2:
Test Methods - Tests A: Cold (IEC 60068-2-1:2007, IDT)
GB/T 2423.2-2008 Environmental Testing for Electric and Electronic Products - Part 2:
Test Methods - Tests B: Dry Heat (IEC 60068-2-2:2007, IDT)
GB/T 2423.3-2006 Environmental Testing for Electric and Electronic Products - Part 2:
Testing Method - Test Cab: Damp Heat, Steady State (IEC 60068-2-78:2001, IDT)
GB/T 2423.10-2008 Environmental Testing for Electric and Electronic Products - Part
2: Tests Methods - Test Fc: Vibration (IEC 60068-2-6:1995, IDT)
GB 4351.1-2005 Portable Fire Extinguishers - Part 1: Performance and Construction
(ISO 7165:1999, NEQ)
3 Terms and Definitions
The following terms and definitions are applicable to this Standard.
3.1 Auto Tracking and Targeting Jet Suppression System
Auto tracking and targeting jet suppression system refers to various indoor and outdoor
fixed jet suppression systems which utilize infrared rays, digital images or other fire
detection components to detect fire and temperature for automatic tracking and
targeting of early fires; adopt the mode of automatic control to implement fire
suppression. The system is constituted of fire suppression device, which is equipped
with detection component and automatic control part, as well as fire-fighting liquid
supply part. The fire suppression device is divided into automatic tracking and targeting
fire cannon suppression device (hereinafter referred to as automatic fire cannon
suppression device) and automatic tracking and targeting jet suppression device
(hereinafter referred to as automatic jet suppression device).
3.2 Targeting Time
Targeting time refers to the time from the start of test fire to the start of system jet.
3.3 Jet Radius
Jet radius refers to the length of the horizontal projection of the fire suppression device
to the farthest jet landing point, or, the radius of the circular projection of the ground
plane of the maximum jet protection range.
3.4 Maximum Protection Radius
Maximum protection radius refers to 90% of the length of the horizontal projection of
the fire suppression device to the farthest jet landing point, or, the radius of the circular
projection of the ground plane of effective spray projection range.
3.5 Monitory Radius
Monitory radius refers to the length of the horizontal projection of the detection
component of the fire suppression device to the center point of test fire that can be
effectively detected.
3.6 Working Pressure
Working pressure refers to fire suppression device?€?s rated outlet pressure.
4 Classification and Model
4.1 Classification
4.1.1 In accordance with flow, it may be classified into:
a) Rated flow is larger than 16 L/s: automatic fire cannon suppression device;
able to normally start and jet.
5.5 Insulation Resistance
In accordance with 6.6, fire suppression device shall receive insulation resistance test.
The insulation resistance between the external live terminals of the fire suppression
device and the casing shall be larger than 20 M???.
5.6 Dielectric Strength
In accordance with 6.7, fire suppression device shall receive dielectric strength test. It
shall be able to withstand voltage test for 1 min under the frequency of 50 Hz and the
voltage of 1,500 V. There shall be no phenomenon of breakdown or flashover.
5.7 Resistance to Ambient Light Interference
In accordance with 6.8, fire suppression device shall receive ambient light interference
test. During the test, the fire suppression device shall not trigger malfunctions, such as
starting and jetting.
5.8 Voltage Fluctuation Adaptability
In accordance with 6.9, fire suppression device shall receive voltage fluctuation
adaptability test. Within the rated voltage range of -10% ~ + 10%, it shall be able to
normally start and function.
5.9 Vibration Resistance
In accordance with 6.10, fire suppression device shall receive vibration resistance test.
After the test, the fire suppression device shall not manifest shedding, cracking or
obvious deformation; it shall be able to normally function.
5.10 Fire Suppression Performance
In accordance with 6.11, fire suppression device shall receive fire suppression
performance test. Starting from automatic jetting, within 3 min, the automatic fire
cannon suppression device and injection-type automatic jet suppression device shall
extinguish Level-1A fire suppression; within 6 min, spraying-type automatic jet
suppression device shall extinguish Level-1A fire suppression.
5.11 Requirements for Automatic Control
5.11.1 Requirements for intelligent detection and targeting and linkage decision
management
Fire suppression device shall be equipped with the function of intelligent detection and
targeting and linkage decision management, which shall be normally functioning.
angle and horizontal slewing angle of fire suppression device. The result shall comply
with the requirements in 5.1.
6.2 Performance Test
6.2.1 Measurement of rated pressure, flow, maximum protection radius, jet
radius and monitoring radius
Fix the fire suppression device at the minimum installation height. On the test pipeline,
install a flowmeter with an accuracy of not lower than ?? 1%; a pressure gauge with an
accuracy of not less than Level-1.6 and a measuring range of (0 ~ 2.5) MPa.
Manually control the nozzle to be in a horizontal state. Turn on the fire suppression
device to let it jet; maintain it at the rated working pressure; then, jet under the rated
pressure. After around 1 min, use a tape with an accuracy of ?? 1 cm to measure the
distance from the farthest trace to the projection directly underneath the nozzle, which
is the jet radius. 90% of the jet radius (rounded off) is the maximum protection radius.
Ignite the test fire; use a tape with an accuracy of ?? 1 cm to measure the length of the
horizontal projection of the center point of the test fire that can be effectively detected
by the detection component of the system, which is the monitoring radius.
The flow may be directly measured through a calibrated flowmeter. Or, in accordance
with the flow of fire suppression device, an appropriate volume of measuring tank may
be selected. Wait till it reaches the rated pressure and becomes stable, turn to the
measuring tank for jetting; the jetting time shall be not less than 30 s; immediately
remove it. Then, measure the volume or the mass of water in the measuring tank.
Through calculation, obtain the flow of the fire suppression device.
The test result shall all comply with the requirements in Table 1.
6.2.2 Measurement of targeting time
Respectively fix the fire suppression device at the minimum installation height and the
maximum installation height. At the measured maximum protection radius, use test fire
to induce the system to initiate the action of targeting, aim at the target and jet. Use an
electronic stopwatch with an accuracy of not lower than ?? 0.1 s to measure the time
from the start of the test fire to the start of the jet of the fire suppression device, which
is the targeting time. The measurement result shall comply with the stipulations in Table
1. The test fire is: add 30 mm height of clean water to a 570 mm diameter oil pan
(height: 70 mm), then, add 500 mL of automotive gasoline; ignite the gasoline on the
oil pan.
6.3 High Temperature Test
In accordance with GB/T 2423.2-2008, conduct the test. Connect the system to the
power supply, so that it could enter the normal monitoring state. Put the fire
6.9 Voltage Fluctuation Adaptability Test
Use a voltage regulator and electrotechnical instrument to respectively adjust the
power supply voltage to ?? 10% of the rated voltage. The test result shall comply with
the requirements in 5.8.
6.10 Vibration Resistance Test
6.10.1 The test method shall comply with the requirements in GB/T 2423.10-2008.
During the test, the fire suppression test shall be in non-working state. The test
conditions shall comply with the following stipulations:
a) Range of frequency cycle: 10 Hz ~ 150 Hz ~ 10 Hz;
b) Amplitude (single amplitude): 0.19 mm;
c) Scanning rate: one octave / min;
d) Vibration direction: three directions: XYZ;
e) Frequency-sweeping number: 2 frequency-sweeping cycles.
6.10.2 In accordance with the result of vibration response, respectively conduct the
test in accordance with the following three circumstances. Each test shall be
successively conducted in the three directions XYZ of the sample:
a) When resonance frequency is not found, at the frequency of 150 Hz, conduct
fixed frequency vibration test with the amplitude of 0.19 mm and the duration
of 10 min;
b) When there are not more than 4 resonance frequencies being found, on each
resonance point, conduct resonance test with the set amplitude of 0.19 mm
and the duration of 10 min;
c) When there are more than 4 resonance frequencies being found, within the
frequency cycle range of 10 Hz ~ 150 Hz ~ 10 Hz, conduct resonance test
with the amplitude of 0.19 mm and the frequency-sweeping rate of double
frequency / min. The duration of resonance is 1 h in each direction.
The test result shall comply with the requirements in 5.9.
6.11 Fire Suppression Test
6.11.1 Automatic fire cannon suppression device and injection-type automatic
jet suppression device
At the minimum installation height and the maximum installation height, respectively
place Level-1A fire test model inside the maximum protection radius of the fire
c) When production is resumed after one year of suspension, or, normal
production exceeds two years;
d) When a national quality supervision institution proposes a request for type
inspection.
7.1.2 The content of type inspection is all the items stipulated in this Standard. The
inspection result shall all satisfy the stipulations of this Standard.
7.1.3 The quantity of test samples for type inspection is 3 sets. The test procedure
shall comply with the stipulations of Appendix A.
7.2 Exit-factory Inspection
7.2.1 Before exiting factory, exit-factory inspection shall be conducted.
7.2.2 Exit-factory inspection shall be conducted in accordance with the stipulations in
5.1, 5.2, 5.3, 5.4, 5.5, 5.6, 5.7, 5.8, 5.9, 5.13 and 5.15. The result shall all comply with
the stipulations of this Standard.
8 Marking, Packaging, Storage, Transportation and
Instruction Manual
8.1 Marking
8.1.1 The nameplate of product shall include the following content: manufacturer name
and trademark, product name, model and specification, serial No. of implemented
standard, product No., working pressure, flow, jet flow radius, maximum protection
radius, monitoring radius, minimum and maximum installation height, etc.
8.1.2 The surface of packaging box shall be printed with product name, specification,
quantity, external dimensions of packaging box, gross weight, manufacturer name,
address and contact information.
8.2 Packaging
The packaging of product shall ensure that product is not damaged or loosened in
normal transportation, and that product complies with user?€?s demands and the
regulations of the transportation department.
8.3 Storage
The storage warehouse shall be well-ventilated, dry and clean. Products shall not be
heavily pressed.
8.4 Transportation
Share